Очень популярная тема (более 25 ответов) Чиллер - большой ремонт (число прочтений - 13260 )
SSA
ЗавсегдатАй форума
---
*
Отсутствует



Сообщений: 1640
Местоположение: Оренбург
Зарегистрирован: 28.03.2009
Re: Чиллер - большой ремонт
Ответ #30 - 19.06.2014 :: 15:10:22
Функции поста
Смотри-ка, какие мы ранимые... Смех

START-UP
Check the main power supplies to the unit are ‘ON’, all refrigerant service valves are open (counter-clockwise one turn short of fully open) and chilled liquid fl ow has been es tab lished (unless the unit chilled liquid pump start con trol is being used, in which case just ensure the pump supply is on). Ensure only the correct system switches (SYS 1-2) on the microprocessor circuit board are in the ‘ON’ position.
Press the ‘STATUS’ key on the keypad and then switch the unit ON/OFF switch below the keypad to the ON position.
The controller will perform a pre-check to ensure that the daily/holiday schedule and any remote interlocks will allow the unit to run, all safety cut-outs are sat is fied and that cooling load is required (i.e. that the chilled liquid temperature is outside the set limits). Any problems found by the pre-check will be displayed if present. If no prob lems are present and cooling duty is required the lead compressor will start.
The display will show the anti-coincidence timer status for the lag compressor, followed by ‘NO COOL LOAD’ until it is called to operate by the control system.

Такой ответ пойдет?
  
Наверх
 
IP записан
 
SSA
ЗавсегдатАй форума
---
*
Отсутствует



Сообщений: 1640
Местоположение: Оренбург
Зарегистрирован: 28.03.2009
Re: Чиллер - большой ремонт
Ответ #31 - 19.06.2014 :: 15:18:04
Функции поста
Вкрались ошибки в копирование. Исправляю:
START-UP
Check the main power supplies to the unit are ‘ON’, all refrigerant service valves are open (counter-clockwise one turn short of fully open) and chilled liquid fl ow has been established (unless the unit chilled liquid pump start control is being used, in which case just ensure the pump supply is on). Ensure only the correct system switches (SYS 1-2) on the microprocessor circuit board are in the ‘ON’ position.
Press the ‘STATUS’ key on the keypad and then switch the unit ON/OFF switch below the keypad to the ON position.
The controller will perform a pre-check to ensure that the daily/holiday schedule and any remote interlocks will allow the unit to run, all safety cut-outs are satisfied and that cooling load is required (i.e. that the chilled liquid temperature is outside the set limits). Any problems found by the pre-check will be displayed if present. If no problems are present and cooling duty is required the lead compressor will start.
The display will show the anti-coincidence timer status for the lag compressor, followed by ‘NO COOL LOAD’ until it is called to operate by the control system.
  
Наверх
 
IP записан
 
Онсий
Член клуба
Холодильщик
*
Отсутствует


Трям!

Сообщений: 2366
Местоположение: Пермь
Зарегистрирован: 04.11.2009
Пол: Мужской
Re: Чиллер - большой ремонт
Ответ #32 - 19.06.2014 :: 16:45:29
Функции поста
ELLIKS писал(а) 19.06.2014 :: 14:19:42:
1. Я вроде попросил помощи.
2. Конкретная проблема. Как выгребал описывать нет смысла.
3. Вопрос что может быть.
4. В современном мире в век интернета даже диагнозы медицинские ставят. А чиллер наверно проще человеческого организма? Проблема в том, что в регионе знахарей много докторов нет. Официалов долго, дорого, а надо срочно. Что может означать эта надпись.

1. И чо?
2. Это будем мы решать. Нужно полное описание всех шагов и действий - личных и каждого предшественника в отдельности. Показания всех датчиков. Настройки. Фотографии... Иначе ничем не отличаешься от предшественников.
3. Не вижу знака вопроса.
4. Да ставят. Но перед этим собирают полный анамнез, с подписями, печатями... Официалы значит долго и дорого?   Улыбка  А хочется быстро и бесплатно?  Смех    Теперь взгляни на это со стороны
Ха-ха   Смех
  
Наверх
IP записан
 
ELLIKS
Малоактивный пользователь
*
Отсутствует



Сообщений: 3
Местоположение: tatarstan
Зарегистрирован: 19.06.2014
Re: Чиллер - большой ремонт
Ответ #33 - 20.06.2014 :: 11:22:12
Функции поста
Отдельное спасибо SSA за внимание и помощь. Оперативно и конкретно.   Очень довольный
Сделал быстро и бесплатно.
  

Не учите меня жить, помогите материально.
Наверх
 
IP записан